Hazardous Area Reference

 

NORTH AMERICAN HAZARD CATEGORY

  ExampleNEC 500-503NEC 505
CLASS I
(Gases and Vapors)
Acetylene
Hydrogen
Ethylene
Propane
Group A
Group B
Group C
Group D
IIC
IIC or IIB+H2
IIB
IIA
CLASS II
(Dusts)
Metal dust
Coal dust
Grain dust
Group E
Group F
Group G
  
 

 

AREA CLASSIFICATION

  Continuous
hazardIntermittent
hazardHazard under
abnormal conditions
NORTH AMERICA  Division 1 Division 1 Division 2
IEC/CENELEC/EUROPE 
/NEC505+
Zone 0
(Zone 20 dust)
Zone 1
(Zone 21 dust)
Zone 2
(Zone 22 dust)
 

 

 

TEMPERATURE CLASSIFICATION

Max. surface
temp.(°C)NEC
Table500-3(d)IEC79-8
T ClassEN 50 014
450°C T1 T1 T1
300°C T2 T2 T2
280°C T2A -- --
260°C T2B -- --
230°C T2C -- --
215°C T2D -- --
200°C T3 T3 T3
180°C T3A -- --
165°C T3B -- --
160°C T3C -- --
135°C T4 T4 T4
120°C T4A -- --
100°C T5 T5 T5
85°C T6 T6 T6
 

 

INGRESS PROTECTION:   (IP) CODES AND NEMA TYPES

FIRST NUMERAL
Protection against solid bodiesSECOND NUMERAL
Protection against liquid
0 - NO PROTECTION 0 - NO PROTECTION
1- OBJECTS EQUAL TO OR GREATER THAN 50 mm 1 - VERTICALLY DRIPPING WATER
2 - OBJECTS EQUAL TO OR GREATER THAN 12.5 mm 2 - 75 TO 105°-ANGLED DRIPPING WATER
3 - OBJECTS EQUAL TO OR GREATER THAN 2.5 mm 3 - SPRAYING WATER
4 - OBJECTS EQUAL TO OR GREATER THAN 1.0 mm 4 - SPLASHING WATER
5 - DUST-PROTECTED 5 - WATER JETS
6 - DUST-TIGHT 6 - HEAVY SEAS, POWERFUL WATER JETS
   7 - EFFECTS OF IMMERSION
   8 - INDEFINITE IMMERSION
 

  

NEMA and UL Types of Enclosures.

Type 3 Enclosure 
Type 3 enclosures are intended for outdoor use primarily to provide a degree of protection against windblown dust, rain, sleet and external ice formation.

Type 3R Enclosure 
Type 3R enclosures are intended for outdoor use primarily to provide a degree of protection against falling rain and external ice formation.

Type 3S Enclosure 
Enclosures are intended for outdoor use primarily to provide a degree
of protection against rain, sleet, windblown dust, and to provide
for operation of external mechanisms when ice laden.

Type 4 Enclosure 
Type 4 enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against windblown dust and rain, splashing water, hose-directed water and external ice formation.

Type 4X Enclosure 
Type 4X enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water, hose-directed water and external ice formation.

Type 7 Enclosure 
Type 7 enclosures are for use indoors in locations classified as Class I, Groups A, B, C or D, as defined in the National Electrical Code®.

Type 9 Enclosure 
Type 9 enclosures are for use in indoor locations classified as Class II, Groups E, F or G, as defined in the National Electrical Code®.

Type 12 Enclosure 
Type 12 enclosures are intended
for indoor use primarily to provide degree of protection against dust, falling dirt and dripping noncorrosive liquids.